Three large cooling towers from a power plant emit white steam against a clear blue sky. The gray towers, adorned with red-and-white patterned tops, stand prominently in the image.

XF150MAx

For applications where extremely low drift ratings are not required, XF150MAx provides a cost-effective solution with drift loss of 0.001%. Its high surface area and nesting design provide maximum performance at minimum pressure drop.

XF150MAx Features

Specifications (XF)

English Metric
ProductBlade Spacing
inches
Depth
inches
Width
inches
Length
Ft
Blade Thickness
(after forming)
mils
Dry Weight
lbs/ft2
Max. Height At 10° From Vertical
Ft
XF80MAx
0.86
5.25
24
2 ,3, 4, 5, 6, 8, 10, 12
131.0612
XF150MAx
1.50
5.25
12, 18
2 ,3, 4, 5, 6, 8, 10, 12
15
20
1.03
1.45
12
ProductBlade Spacing
mm
Depth
mm
Width
mm
Length
kg
Blade Thickness
(after forming)
mm
Dry Weight
kg/m2
Max. Height At 10° From Vertical
m
XF80MAx
21.8
133
610
610, 914, 1219, 1524, 1829, 2438, 3048, 3658
0.335.23.66
XF150MAx
38.1
133
305, 457
610, 914, 1219, 1524, 1829, 2438, 3048, 3658
0.38
0.51
1.03
1.45
3.66
Abstract image featuring a minimalist design of white and light gray geometric shapes. The background has a subtle gradient, creating a clean and modern aesthetic.
Start A Conversation

A Partner You Can Rely On

Complete the form below to learn about the benefits of partnering with Brentwood to maximize your tower’s performance.













    XF150MAx
    X