CF1900
CF1900 is a popular choice for field-erected or factory assembled counterflow towers and can also be used in crossflow towers. It is predominantly used in HVAC and light industrial applications where the water contains low levels of total suspended solids.
Benefits
Highly Efficient
Cross-fluted fills offer the highest level of efficiency of all film fill designs, improving heat transfer and maximizing overall tower performance.
Improved Water Distribution
The engineered microstructure incorporated into cross-fluted fills enhances water distribution and thermal mixing.
Dedicated Bond Points
Brentwood’s cross-fluted fills feature bonded edges for added media strength and durability.
Mechanical Assembly
Brentwood’s Mechanical Assembly technology has been improved for the production of ThermaCross, yielding connections that are 50% stronger than glued.
Cross-Fluted Film Fill Specifications
Products | Surface Area ft2/ft3 | Sheet Spacing inches | Flute Angle Degrees (˚) | Sheets Per Ft | Pack Sizes Minimum D/W/L inches | Pack Sizes Maximum D/W/L inches | Pack Sizes Standard D/W/L inches | Nominal Gauge mils | Dry Weight lbs/ft3 |
---|---|---|---|---|---|---|---|---|---|
CF1200 | 69 | 0.46 | 30 | 26 | D: 3.9 W: 6 L: 12 | D: 11.8 W: 12 L: 120 | D: 11.8 W: 12 L: 48, 72, 96, 120 | 8 or 10 | 2.4 or 2.8 |
ThermaCross | 47 | 0.75 | 22 | 16 | D: 5.9 W: 5.9 L: 12 | D: 23.625 W: 23.625 L: 144 | D: 11.8 or 23.625 W: 11.8 L: 72, 96, 120 | 10 or 15 | 1.7 or 2.4 |
CF1900 | 48 | 0.75 | 31 | 16 | D: 6 W: 6 L: 12 | D: 24 W: 24 L: 12 | D: 12 or 24 W: 12 or 24 L: 48, 72, 96, 120 | 10 or 15 | 1.7 or 2.4 |
CF1900SS | 48 | 0.75 | 27 | 16 | D: 12 W: 6 L: 24 | D: 12 W: 12 L: 72 | D: 12 W: 12 L: 48, 72 | 10 or 15 | 1.7 or 2.4 |
CFS3000 | 31 | 1.18 | 30 | 10 | D: 12 W: 6 L: 12 | D: 24 W: 24 L: 12 | D: 24 W: 12 or 24 L: 48, 72, 96, 120 | 15 | 1.7 |
Products | Surface Area m2/m3 | Sheet Spacing mm | Flute Angle Degrees(˚) | Pack Sizes Minimum D/W/L mm | Pack Sizes Maximum D/W/L mm | Pack Sizes Standard D/W/L mm | Nominal Gauge mm | Dry Weight kg/m3 |
---|---|---|---|---|---|---|---|---|
CF1200 | 226 | 11.7 | 30 | D: 100 W: 153 L: 305 | D: 300 W: 305 L: 3048 | D: 300 W: 305 L: 1220, 1829, 2439, 3048 | 0.20 or 0.25 | 38.4 or 44.9 |
ThermaCross | 154 | 19 | 22 | D: 150 W: 150 L: 305 | D: 600 W: 600 L: 3658 | D: 300 or 600 W: 300 L: 1829, 2439, 3048 | 0.25 or 0.38 | 27.2 or 38.4 |
CF1900 | 157.5 | 19 | 31 | D: 153 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 305 or 610 W: 305 or 610 L: 1220, 1829, 2439, 3048 | 0.25 or 0.38 | 27.2 or 38.4 |
CF1900SS | 157.5 | 19 | 27 | D: 305 W: 153 L: 610 | D: 305 W: 305 L: 1829 | D: 305 W: 305 L: 1220, 1829 | 0.25 or 0.38 | 27.2 or 38.4 |
CFS3000 | 102 | 30.5 | 30 | D: 305 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 610 W: 305 or 610 L: 1220, 1829, 2439, 3048 | 0.38 | 27.2 |