CFS3000
Used in the same applications as CF1900, – field-erected or factory assembled towers – CFS3000 incorporates larger channels for decreased fouling potential in lower quality water. It splits the water stream five times in a 12-inch (305 mm) vertical path, balancing high thermal performance and low pressure drop.
Benefits
Available in material meeting Cooling Technology Institute (CTI) Standard 136
Available with AccuShield technology
Available in PVC and HPVC
Navigate Within Cross-Fluted Fills
Highly Efficient
Cross-fluted fills offer the highest level of efficiency of all film fill designs, improving heat transfer and maximizing overall tower performance.
Improved Water Distribution
The engineered microstructure incorporated into cross-fluted fills enhances water distribution and thermal mixing.
Dedicated Bond Points
Brentwood’s cross-fluted fills feature bonded edges for added media strength and durability.
Cross-Fluted Film Fill Specifications
English
Metric
Products | Surface Area ft2/ft3 | Sheet Spacing inches | Flute Angle Degrees (˚) | Sheets Per Ft | Pack Sizes Minimum D/W/L inches | Pack Sizes Maximum D/W/L inches | Pack Sizes Standard D/W/L inches | Nominal Gauge mils | Dry Weight lbs/ft3 |
---|---|---|---|---|---|---|---|---|---|
CF1200 | 69 | 0.46 | 30 | 26 | D: 3.9 W: 6 L: 12 | D: 11.8 W: 12 L: 120 | D: 11.8 W: 12 L: 48, 72, 96, 120 | 8 10 15 | 2.3 2.7 3.8 |
ThermaCross | 47 | 0.75 | 22 | 16 | D: 5.9 W: 5.9 L: 12 | D: 23.625 W: 23.625 L: 144 | D: 11.8 or 23.625 W: 11.8 L: 72, 96, 120 | 10 15 20 | 1.7 2.4 3.3 |
CF1900 | 48 | 0.75 | 31 | 16 | D: 6 W: 6 L: 12 | D: 24 W: 24 L: 12 | D: 12 or 24 W: 12 or 24 L: 48, 72, 96, 120 | 10 15 20 | 1.7 2.4 3.3 |
CF1900SS | 48 | 0.75 | 27 | 16 | D: 12 W: 6 L: 24 | D: 12 W: 12 L: 72 | D: 12 W: 12 L: 48, 72 | 5 | 4.8 |
CFS3000 | 31 | 1.18 | 30 | 10 | D: 12 W: 6 L: 12 | D: 24 W: 24 L: 12 | D: 24 W: 12 or 24 L: 48, 72, 96, 120 | 15 20 | 1.6 2.2 |
Products | Surface Area m2/m3 | Sheet Spacing mm | Flute Angle Degrees(˚) | Pack Sizes Minimum D/W/L mm | Pack Sizes Maximum D/W/L mm | Pack Sizes Standard D/W/L mm | Nominal Gauge mm | Dry Weight kg/m3 |
---|---|---|---|---|---|---|---|---|
CF1200 | 226 | 11.7 | 30 | D: 100 W: 153 L: 305 | D: 300 W: 305 L: 3048 | D: 300 W: 305 L: 1220, 1829, 2439, 3048 | 0.20 0.25 0.38 | 36.8 43.2 60.9 |
ThermaCross | 154 | 19 | 22 | D: 150 W: 150 L: 305 | D: 600 W: 600 L: 3658 | D: 300 or 600 W: 300 L: 1829, 2439, 3048 | 0.25 0.38 0.51 | 27.2 38.4 52.9 |
CF1900 | 157.5 | 19 | 31 | D: 153 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 305 or 610 W: 305 or 610 L: 1220, 1829, 2439, 3048 | 0.25 0.38 0.51 | 27.2 38.4 52.9 |
CF1900SS | 157.5 | 19 | 27 | D: 305 W: 153 L: 610 | D: 305 W: 305 L: 1829 | D: 305 W: 305 L: 1220, 1829 | 0.13 | 76.9 |
CFS3000 | 102 | 30.5 | 30 | D: 305 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 610 W: 305 or 610 L: 1220, 1829, 2439, 3048 | 0.38 0.51 | 25.6 35.2 |