VF19 PLUS
Used in counterflow towers where total suspended solids levels are high, VF19 PLUS features an engineered microstructure for improved water distribution and thermal mixing. This fill has been tested and accepted by a major U.S. utility in an operating natural draft cooling tower. Its typical applications include the power, refining, chemical, mining, and food processing industries.
Benefits
Available in material meeting Cooling Technology Institute (CTI) Standard 136
Available with AccuShield technology
Navigate Within Vertical-Fluted Fills
Fouling Resistant
Brentwood’s low-fouling fills have been designed to provide a solution for applications with poor water quality, preventing the media from plugging and improving overall tower efficiency.
Dedicated Bond Points
Bonded edges create rigid, self-supporting media modules, ensuring accurate assembly and maximum strength.
Vertical-Fluted Film Fill Specifications
English
Metric
Products | Surface Area ft2/ft3 | Sheet Spacing inches | Flute Angle Degrees (°) | Sheets Per Foot | Media Min. Size D/W/L inches | Media Max. Size D/W/L inches | Media Standard Size D/W/L inches | Nominal Gauge mils | Dry Weight lbs/ft3 |
---|---|---|---|---|---|---|---|---|---|
VF19 PLUS | 47 | 0.75 | 0 | 16 | D: 11.8 W: 6 L: 12 | D: 35.4 W: 24 L: 144 | D: 23.6 W: 12, 24 L: 48, 72, 96, 120 | 10 15 20 | 1.7 2.4 3.3 |
AFVF19 | 42 | 0.76 | 0 | 16 | D: 9.8 W: 3.1 L: 20.1 | D: 39.4 W: 23.3 L: 120.4 | D: 19.7 W: 12.4 L: 80.3, 120.4 | 10 15 20 | 1.6 2.3 3.0 |
VF3800 | 40 | 1.5 | 0 | 16 | D: 24 W: 6 L: 12 | D: 24 W: 24 L: 144 | D: 24 W: 12, 24 L: 48, 72, 96, 120 | 15/22 | 2.6 |
VF5000 | 30 | 2 | 0 | 12 | D: 24 W: 6 L: 12 | D: 24 W: 24 L: 144 | D: 24 W: 12, 24 L: 48, 72, 96, 120 | 15/22 | 2.0 |
KVP 319 | 44 | 0.75 | 0 | 16 | D: 11.8 W: 6 L: 11.8 | D: 23.6 W: 23.9 L: 94.5 | D: 23.6 W: 12 L: 59.1, 70.9, 82.7 | N/A | 5.7 |
Products | Surface Area m2/m3 | Sheet Spacing mm | Flute Angle Degrees (°) | Media Min. Size D/W/L mm | Media Max. Size D/W/L mm | Media Standard Size D/W/L mm | Nominal Gauge mm | Dry Weight kg/m3 |
---|---|---|---|---|---|---|---|---|
VF19 PLUS | 154 | 19 | 0 | D: 300 W: 153 L: 305 | D: 900 W: 610 L: 3658 | D: 600 W: 305, 610 L: 1220, 1829, 2439, 3048 | 0.25 0.38 0.51 | 27.2 38.4 52.9 |
AFVF19 | 138 | 19.4 | 0 | D: 250 W: 79 L: 510 | D: 1000 W: 592 L: 3058 | D: 500 W: 315 L: 2038, 3058 | 0.25 0.38 0.51 | 25.6 36.8 48.1 |
VF3800 | 131 | 38 | 0 | D: 610 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 610 W: 305, 610 L: 1220, 1829, 2439, 3048 | 0.38/0.56 | 41.6 |
VF5000 | 98 | 50 | 0 | D: 610 W: 153 L: 305 | D: 610 W: 610 L: 3658 | D: 610 W: 305, 610 L: 1220, 1829, 2439, 3048 | 0.38/0.56 | 32.0 |
KVP 319 | 144 | 19 | 0 | D: 300 W: 152 L: 300 | D: 600 W: 608 L: 2400 | D: 600 W: 304 L: 1500, 1800, 2100 | N/A | 28 |